socomec NETYS PR/RT/ITYS

NETYS PR/RT/ITYS

Importata da documento

Mappa registri Modbus

41 registri

LenScalaEndian
4096
UPS type
Codice fisso 29 = NETYS UPS.
ups_type3uint1611R
4097
Power
Potenza nominale UPS, formato kVA*10.
power3uint1610.1kVAR
4098
Module
0=system(concentrator), 1-6=moduli.
module3uint1611R
4099
Serial number (char 1-2)
ASCII, LSB=char1 MSB=char2. NETYS PR: fisso a "_UNKNOWN__".
serial_number_char_1_23uint1611R
4100
Serial number (char 3-4)
ASCII, LSB=char3 MSB=char4.
serial_number_char_3_43uint1611R
4101
Serial number (char 5-6)
ASCII, LSB=char5 MSB=char6.
serial_number_char_5_63uint1611R
4102
Serial number (char 7-8)
ASCII, LSB=char7 MSB=char8.
serial_number_char_7_83uint1611R
4103
Serial number (char 9-10)
ASCII, LSB=char9 MSB=char10.
serial_number_char_9_103uint1611R
4108
Jbus code
Versione/revisione protocollo JBUS SICON. NETYS PR: non presente. Bit0-3=JBUS-Version(0x02=JBUS-P), bit4-7=version code, bit8-11=revision code.
jbus_code3uint1611R
4128
States word 0 (S00-S15)
bit0 S00 Input Mains present(Mains OK); bit1 S01 Inverter ON; bit2 S02 Rectifier ON; bit3 S03 Load on Inverter(normal mode); bit4 S04 Load on Mains/Load on Bypass; bit5 S05 Load on Battery/Battery Discharging; bit7 S07 Eco Mode ON; bit8 S08 UPS in Stand-by mode; bit9 S09 Buzzer ON; bit10 S10 Battery Test in progress; bit13 S13 Battery Test supported(1=possibile); bit14 S14 Battery Test failed; bit15 S15 Battery near end of Back-up(Low battery).
states_word_0_s00_s153bitfield11R
4129
States word 1 (S16-S31)
bit0 S16 Battery discharged; bit1 S17 Battery OK(1)/not OK(0); bit7 S23 Inverter synchronised with Mains; bit8 S24 Boost ON; bit10 S26 Auxiliary mains OK; bit11 S27 Battery charger ON(1)/OFF(0); bit12 S28 Auxiliary input frequency out of tolerance; bit15 S31 Battery extension present.
states_word_1_s16_s313bitfield11R
4130
States word 2 (S32-S47)
bit10 S42 The commands control table is managed (if=1).
states_word_2_s32_s473bitfield11R
4160
Alarms word 0 (A00-A15)
bit0 A00 Alarm present(OR di tutti gli allarmi di guasto); bit1 A01 Battery Failure/Battery fuse open; bit2 A02 UPS overload; bit3 A03 Output voltage out of tolerance; bit4 A04 Digital power supply fault(Vcc); bit5 A05 Input voltage out of tolerance; bit6 A06 Auxiliary mains out of tolerance; bit7 A07 Internal over-temperature alarm.
alarms_word_0_a00_a153bitfield11R
4161
Alarms word 1 (A16-A31)
bit2 A18 Overload timeout blocking Inverter; bit6 A22 Input mains general alarm; bit14 A30 UPS stopped for overload; bit15 A31 Imminent Stop.
alarms_word_1_a16_a313bitfield11R
4192
Load phase 1
load_phase_13uint1611%R
4195
Total load
Somma fase1+2+3, diviso numero fasi.
total_load3uint1611%R
4196
Battery capacity / Remaining Battery Capacity
Battery capacity mostrata solo in carica; Remaining Battery Capacity mostrata solo in scarica.
battery_capacity_remaining_battery_capacity3uint1611%R
4198
Auxiliary mains star voltage V1
ATTENZIONE: unita' riportata nel documento originale come "%" (probabile refuso: nella tabella omologa MASTERYS lo stesso segnale M06 ha unita' "V"). Riportato cosi' com'e' nel documento, senza correggere silenziosamente.
auxiliary_mains_star_voltage_v13uint1611%R
4201
Output star voltage V1
output_star_voltage_v13uint1611VR
4207
Output current phase L1
output_current_phase_l13uint1610.1AR
4210
Auxiliary frequency
auxiliary_frequency3uint1610.1HzR
4211
Output frequency
output_frequency3uint1610.1HzR
4212
Positive battery voltage
positive_battery_voltage3uint1610.1VR
4214
Internal UPS temperature
internal_ups_temperature3uint1611°CR
4215
Remaining back-up time
remaining_back_up_time3uint1611minR
4225
Input mains star voltage V1
input_mains_star_voltage_v13uint1611VR
4320
Nominal star input voltage
nominal_star_input_voltage3uint1611VR
4321
Nominal star output voltage
nominal_star_output_voltage3uint1611VR
4322
Nominal input frequency
nominal_input_frequency3uint1611HzR
4323
Nominal output frequency
nominal_output_frequency3uint1611HzR
4324
Firmware version of communication board
Es. 1.00.
firmware_version_of_communication_board3uint1610.01R
4328
Total nominal battery capacity
Incluse eventuali espansioni batteria.
total_nominal_battery_capacity3uint1610.1AhR
4330
Number of Power Share Plugs Available
number_of_power_share_plugs_available3uint1611R
4346
Input mode
1=NORMAL, 2=WIDE. Solo Netys PR.
input_mode3uint1611R
4347
Vout setting
220/230/240. Solo Netys PR.
vout_setting3uint1611VR
4348
Battery extensions
0/1/2. Solo Netys PR.
battery_extensions3uint1611R
4960
Date/Time word 1 (Minutes/Seconds)
MSB=Minuti(0-59), LSB=Secondi(0-59). Disponibile su Netys RT e Itys. 0xFFFF se non disponibile.
date_time_word_1_minutes_seconds3uint1611R/W
4961
Date/Time word 2 (Day/Hour)
MSB=Giorno del mese(1-31), LSB=Ora(0-23).
date_time_word_2_day_hour3uint1611R/W
4962
Date/Time word 3 (Month/Weekday)
MSB=Mese(1-12), LSB=Giorno della settimana(1=lunedì..7=domenica).
date_time_word_3_month_weekday3uint1611R/W
4963
Date/Time word 4 (Year)
LSB=Anno(00-99).
date_time_word_4_year3uint1611R/W
5552
Command code
0x0005 C05 Stand-by Mode enable; 0x0006 C06 Stand-by Mode(UPS ON) disable; 0x0007 C07 Buzzer enable; 0x0008 C08 Buzzer off; 0x000D C13 Mimic panel LED test; 0x000E C14 Buzzer disable; 0x0010 C16 Immediate Battery Test.
command_code6uint1611W