BusBabel

schneider electric-iem3000

electric-iem3000

Importata da documento

Mappa registri Modbus

50 registri

LenScalaEndian
3000
I1:-phase-1-current
I1:-phase-1-current
i1_phase_1_current3float3221AR
3002
I2:-phase-2-current
I2:-phase-2-current
i2_phase_2_current3float3221AR
3004
I3:-phase-3-current
I3:-phase-3-current
i3_phase_3_current3float3221AR
3010
Currentavg
Currentavg
currentavg3float3221AR
3020
Voltage-L1-L2
Voltage-L1-L2
voltage_l1_l23float3221VR
3022
Voltage-L2-L3
Voltage-L2-L3
voltage_l2_l33float3221VR
3024
Voltage-L3-L1
Voltage-L3-L1
voltage_l3_l13float3221VR
3026
Voltage-ll-avg
Voltage-ll-avg
voltage_ll_avg3float3221VR
3028
Voltage-L1-N
Voltage-L1-N
voltage_l1_n3float3221VR
3030
Voltage-L2-N
Voltage-L2-N
voltage_l2_n3float3221VR
3032
Voltage-L3-N
Voltage-L3-N
voltage_l3_n3float3221VR
3036
Voltage-ln-avg
Voltage-ln-avg
voltage_ln_avg3float3221VR
3054
Active-power-phase-1
Active-power-phase-1
active_power_phase_13float3221kWR
3056
Active-power-phase-2
Active-power-phase-2
active_power_phase_23float3221kWR
3058
Active-power-phase-3
Active-power-phase-3
active_power_phase_33float3221kWR
3060
Total-active-power
Total-active-power
total_active_power3float3221kWR
3068
Total-reactive-power-not-applicable-for-iem3150-/-iem3250-/-iem3350
Total-reactive-power-not-applicable-for-iem3150-/-iem3250-/-iem3350
total_reactive_power_not_applicable_for_iem3150_iem3250_iem33503float3221kVARR
3076
Total-apparent-power-not-applicable-for-iem3150-/-iem3250-/-iem3350
Total-apparent-power-not-applicable-for-iem3150-/-iem3250-/-iem3350
total_apparent_power_not_applicable_for_iem3150_iem3250_iem33503float3221kVAR
3084
Total-power-factor:-1-<-pf
Total-power-factor:-1-<-pf
total_power_factor_1_lt_pf3float3221R
3110
Frequency
Frequency
frequency3float3221HzR
3204
Total-active-energy-import
Total-active-energy-import
total_active_energy_import3int6441WhR
3208
Total-active-energy-export-not-applicable-for-iem3150-/-iem3250-/-iem3350
Total-active-energy-export-not-applicable-for-iem3150-/-iem3250-/-iem3350
total_active_energy_export_not_applicable_for_iem3150_iem3250_iem33503int6441WhR
3220
Total-reactive-energy-import-not-applicable-for-iem3150-/-iem3250-/-iem3350
Total-reactive-energy-import-not-applicable-for-iem3150-/-iem3250-/-iem3350
total_reactive_energy_import_not_applicable_for_iem3150_iem3250_iem33503int6441VARhR
3224
Total-reactive-energy-export-not-applicable-for-iem3150-/-iem3250-/-iem3350
Total-reactive-energy-export-not-applicable-for-iem3150-/-iem3250-/-iem3350
total_reactive_energy_export_not_applicable_for_iem3150_iem3250_iem33503int6441VARhR
3256
Partial-active-energy-import
Partial-active-energy-import
partial_active_energy_import3int6441WhR
3272
Partial-reactive-energy-import-not-applicable-for-iem3150-/-iem3250-/-iem3350
Partial-reactive-energy-import-not-applicable-for-iem3150-/-iem3250-/-iem3350
partial_reactive_energy_import_not_applicable_for_iem3150_iem3250_iem33503int6441VARhR
3518
Active-energy-import-phase1
Active-energy-import-phase1
active_energy_import_phase13int6441WhR
3522
Active-energy-import-phase-2
Active-energy-import-phase-2
active_energy_import_phase_23int6441WhR
3526
Active-energy-import-phase-3
Active-energy-import-phase-3
active_energy_import_phase_33int6441WhR
3558
Input-metering-accumulation-not-applicable-for-iem3150-/-iem3250-/-iem3350
Input-metering-accumulation-not-applicable-for-iem3150-/-iem3250-/-iem3350
input_metering_accumulation_not_applicable_for_iem3150_iem3250_iem33503int6441UnitR
3701
Demand-method
Demand-method
demand_method3uint1611R
3702
Demand-interval-duration
Demand-interval-duration
demand_interval_duration3uint1611MinuteR
3766
Active-power-demand
Active-power-demand
active_power_demand3float3221kWR
3770
Active-power-peak-demand
Active-power-peak-demand
active_power_peak_demand3float3221kWR
3782
Reactive-power-demand
Reactive-power-demand
reactive_power_demand3float3221kVARR
3786
Reactive-power-peak-demand
Reactive-power-peak-demand
reactive_power_peak_demand3float3221kVARR
3798
Apparent-power-demand
Apparent-power-demand
apparent_power_demand3float3221kVAR
3802
Apparent-power-peak-demand
Apparent-power-peak-demand
apparent_power_peak_demand3float3221kVAR
3814
Current-I1-demand
Current-I1-demand
current_i1_demand3float3221AR
3818
Current-I1-peak-demand
Current-I1-peak-demand
current_i1_peak_demand3float3221AR
3830
Current-I2-demand
Current-I2-demand
current_i2_demand3float3221AR
3834
Current-I2-peak-demand
Current-I2-peak-demand
current_i2_peak_demand3float3221AR
3846
Current-I3-demand
Current-I3-demand
current_i3_demand3float3221AR
3850
Current-I3-peak-demand
Current-I3-peak-demand
current_i3_peak_demand3float3221AR
3878
Current-avg-demand
Current-avg-demand
current_avg_demand3float3221AR
3882
Current-avg-peak-demand
Current-avg-peak-demand
current_avg_peak_demand3float3221AR
4191
Multitariffs-energy-active-rate-0:-multi-tariff-disabled-1-to-4:-rate-A-to-rate-D-not-applicable-for-iem3150-/-iem3250-/-iem3350-note:-you-can-only-set-the-tariff-using-this-method-if-the-tariff-mode-is-set-to-by-communication
Multitariffs-energy-active-rate-0:-multi-tariff-disabled-1-to-4:-rate-A-to-rate-D-not-applicable-for-iem3150-/-iem3250-/-iem3350-note:-you-can-only-set-the-tariff-using-this-method-if-the-tariff-mode-is-set-to-by-communication
multitariffs_energy_active_rate_0_multi_tariff_disabled_1_to_4_rate_a_to_rate_d_not_applicable_for_iem3150_iem3250_iem3350_note_you_can_only_set_the_tariff_using_this_method_if_the_tariff_mode_is_set_to_by_communication3uint1611R
7274
Digital-input-control-mode
Digital-input-control-mode
digital_input_control_mode3uint1611R
8905
Digital-input-status-(only-bit-1-is-used):-bit
Digital-input-status-(only-bit-1-is-used):-bit
digital_input_status_only_bit_1_is_used_bit3uint1611R
9673
Digital-output-control-mode-status
Digital-output-control-mode-status
digital_output_control_mode_status3uint1611R

Leggi questi registri via API

curl https://busbabel.vercel.app/api/devices/schneider/electric-iem3000/registers?version=v1