Microelettrica Scientifica MC3V-CEI

MC3V-CEI

Importata da documento

Mappa registri Modbus

224 registri

LenScalaEndian
0
Serial Number
14 registri ASCII.
serial_number3string—1—R/W—
14
Protection Description
14 registri ASCII.
protection_description3string—1—R/W—
28
HMI Password
Range 0-9999.
hmi_password3uint1611—R/W—
29
Node Address
node_address3uint1611—R/W—
30
Remote Input Board Number
remote_input_board_number3uint1611—R/W—
31
Remote Output Board Number
remote_output_board_number3uint1611—R/W—
32
IPU Application Version
16 registri ASCII.
ipu_application_version3string—1—R/W—
48
Active SetUp Characteristic
active_setup_characteristic3uint1611—R/W—
30208
Start 27S1
start_27s12boolean11—R—
30209
Trip t27S1
trip_t27s12boolean11—R—
30210
Start 27S2
start_27s22boolean11—R—
30211
Trip t27S2
trip_t27s22boolean11—R—
30212
Start 59S1
start_59s12boolean11—R—
30213
Trip t59S1
trip_t59s12boolean11—R—
30214
Start 59S2
start_59s22boolean11—R—
30215
Trip t59S2
trip_t59s22boolean11—R—
30216
Start 59Vo
start_59vo2boolean11—R—
30217
Trip 59Vo
trip_59vo2boolean11—R—
30218
Start 81U
Simbolo originale: "81<".
start_81u2boolean11—R—
30219
Trip 81U
Simbolo originale: "81<".
trip_81u2boolean11—R—
30220
Start 81O
Simbolo originale: "81>".
start_81o2boolean11—R—
30221
Trip 81O
Simbolo originale: "81>".
trip_81o2boolean11—R—
30222
IRF (Internal relay failure)
irf_internal_relay_failure2boolean11—R—
30223
OL_LOCKOUT - LOCKOUT
ol_lockout_lockout2boolean11—R—
30224
OL_RCL_CMD - Recloser Command
ol_rcl_cmd_recloser_command2boolean11—R—
30225
OL_CRC - CRC
ol_crc_crc2boolean11—R—
30226
OL_FR - FR
ol_fr_fr2boolean11—R—
30227
OL_ENRCL - ENRCL
ol_enrcl_enrcl2boolean11—R—
30228
CBOpen - Cmd Open Breaker
cbopen_cmd_open_breaker2boolean11—R—
30229
CBClose - Cmd Close Breaker
cbclose_cmd_close_breaker2boolean11—R—
30230
Start Remote Trip (TS)
start_remote_trip_ts2boolean11—R—
30231
Remote Trip (tTS)
remote_trip_tts2boolean11—R—
30232
BF (Breaker failure)
bf_breaker_failure2boolean11—R—
30233
HwRecov. - HW recovery
hwrecov_hw_recovery2boolean11—R—
30234
Diag850
diag8502boolean11—R—
30235
81Dis - 81f disabled by voltage absence
81dis_81f_disabled_by_voltage_absence2boolean11—R—
30236
Von (Voltage presence)
von_voltage_presence2boolean11—R—
30237
ChS (Logical Output)
chs_logical_output2boolean11—R—
30238
CmdL ON
cmdl_on2boolean11—R—
30720
Logical Outputs word 0
bit0 Start 27S1; bit1 Trip t27S1; bit2 Start 27S2; bit3 Trip t27S2; bit4 Start 59S1; bit5 Trip t59S1; bit6 Start 59S2; bit7 Trip t59S2; bit8 Start 59Vo; bit9 Trip 59Vo; bit10 Start 81U; bit11 Trip 81U; bit12 Start 81O; bit13 Trip 81O; bit14 IRF; bit15 OL_LOCKOUT.
logical_outputs_word_04bitfield11—R—
30721
Logical Outputs word 1
bit0 OL_RCL_CMD; bit1 OL_CRC; bit2 OL_FR; bit3 OL_ENRCL; bit4 CBOpen; bit5 CBClose; bit6 Start Remote Trip(TS); bit7 Remote Trip(tTS); bit8 BF; bit9 HwRecov.; bit10 Diag850; bit11 81Dis; bit12 Von; bit13 ChS; bit14 CmdL ON; bit15 non usato.
logical_outputs_word_14bitfield11—R—
40960
Device Healthy Status
bit0 ALU fail; bit1 ADC fail; bit2 E2prom fail; bit3 Ram fail; bit4 Watch Dog Recovery; bit5 CAN Fail; bit6 Field Fail.
device_healthy_status4bitfield11—R—
1024
V1 (Rated Primary Voltage phase VT, Ph-Ph)
Range 0.05-500 kV, step 0.01.
v1_rated_primary_voltage_phase_vt_ph_ph3uint1610.01kVR/W—
1025
V2 (Rated Secondary Voltage phase VT, Ph-Ph)
Range 100-440 V, step 0.01.
v2_rated_secondary_voltage_phase_vt_ph_ph3uint1610.01VR/W—
1026
Vo1 (Rated Primary Voltage VT Ph-N)
Range 0.05-500 kV, step 0.01.
vo1_rated_primary_voltage_vt_ph_n3uint1610.01kVR/W—
1027
Vo2 (Rated Secondary Voltage VT Ph-N)
Range 50-115 V, step 0.01.
vo2_rated_secondary_voltage_vt_ph_n3uint1610.01VR/W—
1028
Freq (System Frequency)
Range 50-60, step 10 (=5-6 in unita' di 10Hz? riportato letteralmente come nel documento).
freq_system_frequency3uint1611HzR/W—
41472
Led Status
bit0 Led D steady(yellow); bit1 Led C steady(red); bit2 Led B steady(red); bit3 Led A steady(green); bit4 Led D blinking(yellow); bit5 Led C blinking(red); bit6 Led B blinking(red); bit7 Led A blinking(green).
led_status4bitfield11—R—
12288
27S1 trip counter
27s1_trip_counter4uint1611—R—
12289
27S2 trip counter
27s2_trip_counter4uint1611—R—
12290
59S1 trip counter
59s1_trip_counter4uint1611—R—
12291
59S2 trip counter
59s2_trip_counter4uint1611—R—
12292
59Vo trip counter
59vo_trip_counter4uint1611—R—
12293
81U trip counter
Simbolo originale: "81<".
81u_trip_counter4uint1611—R—
12294
81O trip counter
Simbolo originale: "81>".
81o_trip_counter4uint1611—R—
12295
IRF trip counter
Internal Relay Failure.
irf_trip_counter4uint1611—R—
12296
RCL1 - Reclosure Counter 1
rcl1_reclosure_counter_14uint1611—R—
12297
RCL2 - Reclosure Counter 2
rcl2_reclosure_counter_24uint1611—R—
12298
RCL3 - Reclosure Counter 3
rcl3_reclosure_counter_34uint1611—R—
12299
RCL4 - Reclosure Counter 4
rcl4_reclosure_counter_44uint1611—R—
12300
RCLF - Reclosure Counter Failed
rclf_reclosure_counter_failed4uint1611—R—
12301
TS - Remote Trip (contatore)
ts_remote_trip_contatore4uint1611—R—
12302
BF - Breaker Failure trip (contatore)
Il documento originale usa il refuso "Breacker".
bf_breaker_failure_trip_contatore4uint1611—R—
12303
HR - Hardware Recovery (contatore)
hr_hardware_recovery_contatore4uint1611—R—
12304
CB_OpC - Breaker Operation Counter
cb_opc_breaker_operation_counter4uint1611—R—
12305
CB_Swtch - Auxiliary Breaker Operation Counter
cb_swtch_auxiliary_breaker_operation_counter4uint1611—R—
4096
VA (measure)
Tensione concatenata/fase A.
va_measure4uint3221VR—
4098
VB (measure)
vb_measure4uint3221VR—
4100
VC (measure)
vc_measure4uint3221VR—
4102
Vo (measure)
Zero Sequence Voltage.
vo_measure4uint3221VR—
4104
F (measure)
Frequenza.
f_measure4uint3220.001HzR—
4106
p (Period)
p_period4uint3221µsR—
4108
ff (Freerun-Frequency)
ff_freerun_frequency4uint3220.001HzR—
4110
fp (Freerun-Period)
fp_freerun_period4uint3221µsR—
4112
Vd (measure)
Positive sequence component.
vd_measure4uint3221%R—
4114
Vi (measure)
Negative sequence component.
vi_measure4uint3221%R—
34816
Device Version
device_version4uint1611—R—
34817
SWCore Version
swcore_version4uint1611—R—
34818
Protection Library Version
protection_library_version4uint1611—R—
34819
Protection Library Release
1 carattere ASCII.
protection_library_release4string—1—R—
45056
Relay 1 Setup - Link Type
0=NotLink, 1=DirectLink, 2=ComplexLink. Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_link_type3uint1611—R/W—
45057
Relay 1 Setup - Command Type
0=Normally Open, 1=Normally Closed. Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_command_type3uint1611—R/W—
45059
Relay 1 Setup - Relay Type
1=Bistable (unico valore supportato). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_relay_type3uint1611—R/W—
45060
Relay 1 Setup - Automation Operator Type
0=NotUsed, 1=OR, 2=AND. Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_automation_operator_type3uint1611—R/W—
45061
Relay 1 Setup - Operator Number
0 se NotLink, 1 se DirectLink, 2-10 se ComplexLink. Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_operator_number3uint1611—R/W—
45062
Relay 1 Setup - Logical Output Link 0
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_03uint1611—R/W—
45063
Relay 1 Setup - Logical Output Link 1
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_13uint1611—R/W—
45064
Relay 1 Setup - Logical Output Link 2
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_23uint1611—R/W—
45065
Relay 1 Setup - Logical Output Link 3
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_33uint1611—R/W—
45066
Relay 1 Setup - Logical Output Link 4
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_43uint1611—R/W—
45067
Relay 1 Setup - Logical Output Link 5
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_53uint1611—R/W—
45068
Relay 1 Setup - Logical Output Link 6
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_63uint1611—R/W—
45069
Relay 1 Setup - Logical Output Link 7
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_73uint1611—R/W—
45070
Relay 1 Setup - Logical Output Link 8
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_83uint1611—R/W—
45071
Relay 1 Setup - Logical Output Link 9
Riferimento a un ID Logical Output (tabella: 0=27S1,1=t27S1,2=27S2,3=t27S2,4=59S1,5=t59S1,6=59S2,7=t59S2,8=59Vo,9=t59Vo,10=81U,11=t81U,12=81O,13=t81O,14=IRF,15=LOCKOUT,16=CmdRich,17=CRC,18=FR,19=AbRCL,20=CBOpen,21=CBClose,22=TS,23=tTS,24=BF,25=HwRecov.,26=Diag850,27=81Dis,28=Von,29=ChS,30=CmdL ON). Relay 2-8 ripetono la stessa struttura a partire rispettivamente dagli indirizzi 45072, 45088, 45104, 45120, 45136, 45152, 45168 (offset +16 per relè).
relay_1_setup_logical_output_link_93uint1611—R/W—
5120
Date Time - Year
Formato BCD 00YY.
date_time_year3uint1611—R/W—
5121
Date Time - Months/Days
Formato BCD MMDD.
date_time_months_days3uint1611—R/W—
5122
Date Time - Hours/Minutes
Formato BCD hhmm.
date_time_hours_minutes3uint1611—R/W—
5123
Date Time - Seconds/Centiseconds
Formato BCD SSTT.
date_time_seconds_centiseconds3uint1611—R/W—
36864
Command
0=CNT=0 (comando nullo/reset contatore); 1=LedTest; 2=Riarmo (Reset); 3=Start Recording (startREC); 4=Apri Interruttore (ApInt); 5=Chiudi Interruttore (ChInt); 6=Gruppo 2 OFF; 7=Gruppo 2 ON.
command16uint1611—W—
8192
Enable of 27S1
Mirror Banco 2 (Setting Group 2) all'indirizzo 10240.
enable_of_27s13boolean11—R/W—
8193
Enable of 27S2
Mirror Banco 2 (Setting Group 2) all'indirizzo 10241.
enable_of_27s23boolean11—R/W—
8194
Enable of 59S1
Mirror Banco 2 (Setting Group 2) all'indirizzo 10242.
enable_of_59s13boolean11—R/W—
8195
Enable of 59S2
Mirror Banco 2 (Setting Group 2) all'indirizzo 10243.
enable_of_59s23boolean11—R/W—
8196
Enable of 59Vo
Mirror Banco 2 (Setting Group 2) all'indirizzo 10244.
enable_of_59vo3boolean11—R/W—
8197
Enable of 81U (Under-frequency)
Simbolo originale nel documento: "81<". Mirror Banco 2 (Setting Group 2) all'indirizzo 10245.
enable_of_81u_under_frequency3boolean11—R/W—
8198
Enable of 81O (Over-frequency)
Simbolo originale nel documento: "81>". Mirror Banco 2 (Setting Group 2) all'indirizzo 10246.
enable_of_81o_over_frequency3boolean11—R/W—
8201
Enable of Trend
Non presente nel banco 2.
enable_of_trend3boolean11—R/W—
8202
Enable of RCL
Non presente nel banco 2.
enable_of_rcl3boolean11—R/W—
8203
Enable of TS
Non presente nel banco 2.
enable_of_ts3boolean11—R/W—
8204
Enable of BF
Non presente nel banco 2.
enable_of_bf3boolean11—R/W—
8205
Enable of Osc
Non presente nel banco 2.
enable_of_osc3boolean11—R/W—
8207
Enable of 850
Non presente nel banco 2.
enable_of_8503boolean11—R/W—
8210
Enable of ChS
Mirror Banco 2 (Setting Group 2) all'indirizzo 10258.
enable_of_chs3boolean11—R/W—
8704
Blocking Input 1 (BI)
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10752.
blocking_input_1_bi3uint1611—R/W—
8705
Blocking Input 2 (BI)
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10753.
blocking_input_2_bi3uint1611—R/W—
8706
Blocking Input 3 (BI)
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10754.
blocking_input_3_bi3uint1611—R/W—
8707
Blocking Input 4 (BI)
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10755.
blocking_input_4_bi3uint1611—R/W—
8708
Blocking Input 5 (BI)
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10756.
blocking_input_5_bi3uint1611—R/W—
8709
Blocking Input 6 (BI)
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10757.
blocking_input_6_bi3uint1611—R/W—
8710
Blocking Input 7 (BI)
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10758.
blocking_input_7_bi3uint1611—R/W—
8711
OpIRF (Trip Option)
0=NoTrip, 1=Trip.
opirf_trip_option3uint1611—R/W—
8712
Tnum (Reclosure shot number)
0=1, 1=2, 2=3, 3=4.
tnum_reclosure_shot_number3uint1611—R/W—
8713
R1-27 (Enable reclosure on F27S1 trip)
0=No, 1=Si.
r1_27_enable_reclosure_on_f27s1_trip3uint1611—R/W—
8714
R2-27 (Enable reclosure on F27S2 trip)
0=No, 1=Si.
r2_27_enable_reclosure_on_f27s2_trip3uint1611—R/W—
8715
R1-59 (Enable reclosure on F59S1 trip)
0=No, 1=Si.
r1_59_enable_reclosure_on_f59s1_trip3uint1611—R/W—
8716
R2-59 (Enable reclosure on F59S2 trip)
0=No, 1=Si.
r2_59_enable_reclosure_on_f59s2_trip3uint1611—R/W—
8717
R-59o (Enable reclosure on F59Vo trip)
0=No, 1=Si.
r_59o_enable_reclosure_on_f59vo_trip3uint1611—R/W—
8718
R-81U (Enable reclosure on F81U trip)
0=No, 1=Si. Simbolo originale: "R-81<".
r_81u_enable_reclosure_on_f81u_trip3uint1611—R/W—
8719
R-81O (Enable reclosure on F81O trip)
0=No, 1=Si. Simbolo originale: "R-81>".
r_81o_enable_reclosure_on_f81o_trip3uint1611—R/W—
8720
R-TS (Enable reclosure on TS)
0=No, 1=Si.
r_ts_enable_reclosure_on_ts3uint1611—R/W—
8721
InLev (Input Level)
0=Alto, 1=Basso.
inlev_input_level3uint1611—R/W—
8722
TrR (Output relay programmed)
0=Rele1, 1=Rele2, 2=Rele3, 3=Rele4.
trr_output_relay_programmed3uint1611—R/W—
8723
Trg (Trigger)
0=Disab., 1=Avviamento, 2=Scatto, 3=Ingresso Esterno.
trg_trigger3uint1611—R/W—
8724
LBd (Local Baud Rate RS232)
0=9600, 1=19200, 2=38400, 3=57600.
lbd_local_baud_rate_rs2323uint1611—R/W—
8725
RBd (Remote Port Communication)
0=9600, 1=19200, 2=61850.
rbd_remote_port_communication3uint1611—R/W—
8726
RMd (Remote port settings RS485)
0=8.n.1, 1=8.o.1, 2=8.e.1.
rmd_remote_port_settings_rs4853uint1611—R/W—
8727
RPr (Remote port Protocol RS485)
0=Modbus.
rpr_remote_port_protocol_rs4853uint1611—R/W—
8728
Trasf (Voltage transformer type)
0=Bassa, 1=Alta.
trasf_voltage_transformer_type3uint1611—R/W—
8729
MODO (Mode)
0=Trifase, 1=Monofase.
modo_mode3uint1611—R/W—
8730
Key (Buzzer Beep on push key)
0=BeepOFF, 1=BeepON.
key_buzzer_beep_on_push_key3uint1611—R/W—
8731
BkL (Backlight LCD)
0=Auto, 1=Accesa.
bkl_backlight_lcd3uint1611—R/W—
8732
InLv (Input Level, duplicato)
0=Alto, 1=Basso. Il documento originale riporta questo parametro come quasi-duplicato di "InLev" (indirizzo 8721) con spelling diverso: probabile refuso, trascritto cosi' com'e'. Mirror Banco 2 a 10780.
inlv_input_level_duplicato3uint1611—R/W—
8733
AbVd
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10781.
abvd3uint1611—R/W—
8734
AbVi
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10782.
abvi3uint1611—R/W—
8735
AbVo
0=Disabilitato, 1=Abilitato. Mirror Banco 2 a 10783.
abvo3uint1611—R/W—
9216
27S1 (Trip Level)
Range 20-120 %Vn. Mirror Banco 2 a 11264.
27s1_trip_level3uint1611%VnR/W—
9217
27S2 (Trip Level)
Range 5-120 %Vn. Mirror Banco 2 a 11265.
27s2_trip_level3uint1611%VnR/W—
9218
59S1 (Trip Level)
Range 50-150 %Vn. Mirror Banco 2 a 11266.
59s1_trip_level3uint1611%VnR/W—
9219
59S2 (Trip Level)
Range 50-150 %Vn. Mirror Banco 2 a 11267.
59s2_trip_level3uint1611%VnR/W—
9220
59o (Trip Level, 59Vo)
Range 2-100 %Vn. Mirror Banco 2 a 11268.
59o_trip_level_59vo3uint1611%VnR/W—
9221
81U (Trip Level, Under-frequency)
Range 45-65 Hz. Simbolo originale: "81<". Mirror Banco 2 a 11269.
81u_trip_level_under_frequency3uint1610.01HzR/W—
9222
81O (Trip Level, Over-frequency)
Range 45-65 Hz. Simbolo originale: "81>". Mirror Banco 2 a 11270.
81o_trip_level_over_frequency3uint1610.01HzR/W—
9223
81e (Level)
Range 10-50 %Vn.
81e_level3uint1611%VnR/W—
9224
Von (Presence Voltage)
Range 1-100 %Vn.
von_presence_voltage3uint1611%VnR/W—
9225
Vo (Setting selection, Levels)
Range 2-100 %Vn. Mirror Banco 2 a 11273.
vo_setting_selection_levels3uint1611%VnR/W—
9226
Vi (Levels)
Range 100-10000 %. Mirror Banco 2 a 11274.
vi_levels3uint1611%R/W—
9227
Vd (Levels)
Range 2000-10000 %. Mirror Banco 2 a 11275.
vd_levels3uint1611%R/W—
9728
27t1 (Trip Time 27S1)
Range 0.05-60s. Mirror Banco 2 a 11776.
27t1_trip_time_27s13uint1610.01sR/W—
9729
27t2 (Trip Time 27S2)
Range 0.05-60s. Mirror Banco 2 a 11777.
27t2_trip_time_27s23uint1610.01sR/W—
9730
59t1 (Trip Time 59S1)
Range 0.05-60s. Mirror Banco 2 a 11778.
59t1_trip_time_59s13uint1610.01sR/W—
9731
59t2 (Trip Time 59S2)
Range 0.05-60s. Mirror Banco 2 a 11779.
59t2_trip_time_59s23uint1610.01sR/W—
9732
t59o (Trip Time 59Vo)
Range 0.05-60s. Mirror Banco 2 a 11780.
t59o_trip_time_59vo3uint1610.01sR/W—
9733
t81U (Trip Time 81U)
Range 0.05-60s. Simbolo originale: "t81<". Mirror Banco 2 a 11781.
t81u_trip_time_81u3uint1610.01sR/W—
9734
t81O (Trip Time 81O)
Range 0.05-60s. Simbolo originale: "t81>". Mirror Banco 2 a 11782.
t81o_trip_time_81o3uint1610.01sR/W—
9735
tLP (Scan time)
Range 1-650 min.
tlp_scan_time3uint1610.01minR/W—
9736
RCLtr (Reclaim Time)
Range 0.1-60s.
rcltr_reclaim_time3uint1610.01sR/W—
9737
tWait (Reclosure waiting time)
Range 0-60s.
twait_reclosure_waiting_time3uint1610.01sR/W—
9738
tEn (Enable reclosure command time)
Range 0.1-6s.
ten_enable_reclosure_command_time3uint1610.01sR/W—
9739
RCLt1 (Waiting time 1st reclose shot)
Range 0.1-300s.
rclt1_waiting_time_1st_reclose_shot3uint1610.01sR/W—
9740
RCLt2 (Waiting time 2nd reclose shot)
Range 0.1-300s.
rclt2_waiting_time_2nd_reclose_shot3uint1610.01sR/W—
9741
RCLt3 (Waiting time 3rd reclose shot)
Range 0.1-300s.
rclt3_waiting_time_3rd_reclose_shot3uint1610.01sR/W—
9742
RCLt4 (Waiting time 4th reclose shot)
Range 0.1-300s.
rclt4_waiting_time_4th_reclose_shot3uint1610.01sR/W—
9743
tTS (Trip Time, Remote Trip)
Range 0-10s.
tts_trip_time_remote_trip3uint1610.01sR/W—
9744
tBF (Trip time delay, Breaker Failure)
Range 0.05-0.75s.
tbf_trip_time_delay_breaker_failure3uint1610.01sR/W—
9745
tPre (Recording time before Trigger)
Range 0.1-0.5s.
tpre_recording_time_before_trigger3uint1610.01sR/W—
9746
tPost (Recording time after Trigger)
Range 0.1-1.5s.
tpost_recording_time_after_trigger3uint1610.01sR/W—
9747
t_IEC
Range 1-60s.
t_iec3uint1610.01sR/W—
9748
t81e (enable 81f delay on VA presence)
Range 0-0.2s.
t81e_enable_81f_delay_on_va_presence3uint1610.01sR/W—
9749
tCh
Range 0-300s. Mirror Banco 2 a 11797.
tch3uint1610.01sR/W—
24576
Number of last Trip Recorded
Range 0-20.
number_of_last_trip_recorded4uint1611—R—
24577
Last Trip (0) - Presence
0=Absent, 1=Present. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_presence4boolean11—R—
24578
Last Trip (0) - Cause
Riferimento alla tabella FunctionId: 1=27S1,2=27S2,3=59S1,4=59S2,5=59Vo,6=81U,7=81O,8=DbS,9=IRF,10=Trend,11=RCL,12=TS,13=BF,14=Osc,15=Comm,16=850,17=Misc,18=LCD,19=ChS. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_cause4uint1611—R—
24579
Last Trip (0) - VA
Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_va4uint3221VR—
24581
Last Trip (0) - VB
Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_vb4uint3221VR—
24583
Last Trip (0) - VC
Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_vc4uint3221VR—
24585
Last Trip (0) - Vo
Zero Sequence Voltage. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_vo4uint3221VR—
24587
Last Trip (0) - F
Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_f4uint3220.001HzR—
24589
Last Trip (0) - Vd
Positive sequence component. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_vd4uint3221%R—
24591
Last Trip (0) - Vi
Negative sequence component. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_vi4uint3221%R—
24593
Last Trip (0) - Timestamp Year
Formato BCD 00YY. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_timestamp_year4uint1611—R—
24594
Last Trip (0) - Timestamp Months/Days
Formato BCD MMDD. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_timestamp_months_days4uint1611—R—
24595
Last Trip (0) - Timestamp Hours/Minutes
Formato BCD hhmm. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_timestamp_hours_minutes4uint1611—R—
24596
Last Trip (0) - Timestamp Seconds/Centiseconds
Formato BCD SSTT. Last Trip (0) = ultimo evento registrato. I record (-1)...(-19) precedenti ripetono la stessa struttura a partire dagli indirizzi 24597, 24617, ... (offset +20 per record), fino a un massimo di 20 record.
last_trip_0_timestamp_seconds_centiseconds4uint1611—R—
28672
Input 1
input_12boolean11—R—
28673
Input 2
input_22boolean11—R—
28674
Input 3
input_32boolean11—R—
28675
Input 4
input_42boolean11—R—
28676
Input 5
input_52boolean11—R—
28677
Input 6
input_62boolean11—R—
28678
Input 7
input_72boolean11—R—
28679
Input 8
input_82boolean11—R—
29184
Relay 1
0=Off, 1=On.
relay_11boolean11—R—
29185
Relay 2
0=Off, 1=On.
relay_21boolean11—R—
29186
Relay 3
0=Off, 1=On.
relay_31boolean11—R—
29187
Relay 4
0=Off, 1=On.
relay_41boolean11—R—
29188
Relay 5
0=Off, 1=On.
relay_51boolean11—R—
29189
Relay 6
0=Off, 1=On.
relay_61boolean11—R—
29190
Relay 7
0=Off, 1=On.
relay_71boolean11—R—
29191
Relay 8
0=Off, 1=On.
relay_81boolean11—R—
29696
Bi27S1 - blocking input 27S1
bi27s1_blocking_input_27s12boolean11—R—
29697
Bi27S2 - blocking input 27S2
Il documento originale riporta per refuso la descrizione "blocking input 27S1" anche per questo registro; corretto qui in "27S2" per coerenza col nome del tag, senza alterarne l'indirizzo/funzione.
bi27s2_blocking_input_27s22boolean11—R—
29698
Bi59S1 - blocking input 59S1
bi59s1_blocking_input_59s12boolean11—R—
29699
Bi59S2 - blocking input 59S2
bi59s2_blocking_input_59s22boolean11—R—
29700
Bi59Vo - blocking input 59Vo
bi59vo_blocking_input_59vo2boolean11—R—
29701
Bi81U - blocking input 81U
Simbolo originale: "Bi81<".
bi81u_blocking_input_81u2boolean11—R—
29702
Bi81O - blocking input 81O
Simbolo originale: "Bi81>".
bi81o_blocking_input_81o2boolean11—R—
29703
douSet - double Setup logical input
douset_double_setup_logical_input2boolean11—R—
29704
BiRCL - blocking input RCL
bircl_blocking_input_rcl2boolean11—R—
29705
TS (Logical Input) - Remote trip input
ts_logical_input_remote_trip_input2boolean11—R—
29706
StsBrk - sts Inter.
stsbrk_sts_inter2boolean11—R—
29707
ExtTrgOsc - Oscillo trigger logical input
exttrgosc_oscillo_trigger_logical_input2boolean11—R—
29708
StsSwt
stsswt2boolean11—R—
64647
Exclusive relay id
Valore fisso identificativo del tipo di protezione: 20068 = MC3VCEI.
exclusive_relay_id4uint1611—R—