Delta Electronics DVP series PLCs
DVP series PLCs
Delta Electronics DVP series PLCs (plc, controllori e i/o) ha una mappa Modbus di 16 registri. Function code usati: 1 (coil), 2 (discrete input), 3 (holding register). Tipi di dato: boolean, int32, uint16. Esempi: S0 all'indirizzo 0 (FC 1, boolean); X0 all'indirizzo 1024 (FC 2, boolean); Y0 all'indirizzo 1280 (FC 1, boolean); T0 contact all'indirizzo 1536 (FC 1, boolean).
PLC, controllori e I/OCommunity
Mappa registri Modbus
10 registri
- FC
- 1
- Tipo
- boolean
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 2
- Tipo
- boolean
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 1
- Tipo
- boolean
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 1
- Tipo
- boolean
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 3
- Tipo
- int32
- Unità
- —
- Scala
- 1
- Len
- 2
- Accesso
- R/W
- FC
- 1
- Tipo
- boolean
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 1
- Tipo
- boolean
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 1
- Tipo
- boolean
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
| Len | Scala | Endian | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 0 | S0 First step relay; S0 to S1023 follow one after the other. | s0 | 1 | boolean | 1 | 1 | — | R/W | big | |
| 1024 | X0 First digital input. X is octal: X7 is followed by X10, so Xn is at 0x0400 + the octal number read as a plain count. | x0 | 2 | boolean | 1 | 1 | — | R | big | |
| 1280 | Y0 First digital output. Y is octal like X. | y0 | 1 | boolean | 1 | 1 | — | R/W | big | |
| 1536 | T0 contact Contact of timer T0; T0 to T255 follow one after the other. | t0_contact | 1 | boolean | 1 | 1 | — | R | big | |
| 1536 | T0 current value Current value of timer T0 (16-bit); T255 is at 0x06FF. | t0_current_value | 3 | uint16 | 1 | 1 | — | R/W | big | |
| 1792 | C200 current value Current value of 32-bit counter C200, two registers each; C201 is at 0x0702 and C255 at 0x076E. | c200_current_value | 3 | int32 | 2 | 1 | — | R/W | big_word_swap | |
| 2048 | M0 First auxiliary relay; M0 to M1535 run from 0x0800 to 0x0DFF. | m0 | 1 | boolean | 1 | 1 | — | R/W | big | |
| 3584 | C0 contact Contact of 16-bit counter C0; C0 to C199 run from 0x0E00 to 0x0EC7. | c0_contact | 1 | boolean | 1 | 1 | — | R | big | |
| 3584 | C0 current value Current value of 16-bit counter C0; C199 is at 0x0EC7. | c0_current_value | 3 | uint16 | 1 | 1 | — | R/W | big | |
| 3784 | C200 contact Contact of 32-bit counter C200; C200 to C255 run from 0x0EC8 to 0x0EFF. | c200_contact | 1 | boolean | 1 | 1 | — | R | big |
Stai vedendo 10 registri su 16.
La mappa completa è riservata agli utenti registrati. La registrazione è gratuita.