Belimo Air/Water Actuator
Air/Water Actuator
Belimo Air/Water Actuator (plc, controllori e i/o) ha una mappa Modbus di 27 registri. Function code usati: 3 (holding register). Tipi di dato: boolean, uint16. Esempi: Setpoint all'indirizzo 0 (FC 3, uint16, %); Override control all'indirizzo 1 (FC 3, uint16); Command all'indirizzo 2 (FC 3, uint16); Actuator type all'indirizzo 3 (FC 3, uint16).
PLC, controllori e I/ODa documento
Mappa registri Modbus
10 registri
- FC
- 3
- Tipo
- uint16
- Unità
- %
- Scala
- 0.01
- Len
- 1
- Accesso
- R/W
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R/W
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- %
- Scala
- 0.01
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- %
- Scala
- 0.01
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
- FC
- 3
- Tipo
- uint16
- Unità
- —
- Scala
- 1
- Len
- 1
- Accesso
- R
| Len | Scala | Endian | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 0 | Setpoint Scaled between Min (106) and Max (107). Factory 0 | setpoint | 3 | uint16 | 1 | 0.01 | % | R/W | big_word_swap | |
| 1 | Override control Fast open and fast close increase mechanical wear; use only for time-critical events such as frost protection | override_control | 3 | uint16 | 1 | 1 | — | R/W | big_word_swap | |
| 2 | Command Returns to None after the command; Reset clears the malfunction and service information | command | 3 | uint16 | 1 | 1 | — | R/W | big_word_swap | |
| 3 | Actuator type | actuator_type | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 4 | Relative position | relative_position | 3 | uint16 | 1 | 0.01 | % | R | big_word_swap | |
| 5 | Absolute position Degrees for rotary actuators, millimetres for linear ones | absolute_position | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 8 | Sensor 1 value Unit depends on Sensor 1 type (107): mV (Active), ohm (Passive), 0/1 (Switch), °C or °F x 10 for temperature sensors (0.1 scaling) | sensor_1_value | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 12 | Analog setpoint Setpoint when the actuator is controlled by an analog signal | analog_setpoint | 3 | uint16 | 1 | 0.01 | % | R | big_word_swap | |
| 99 | Bus termination 120 ohm termination; set with the configuration tools | bus_termination | 3 | uint16 | 1 | 1 | — | R | big_word_swap | |
| 100 | Series number, 1st part Example 00839-31324-064-008: 1st part 00839 | series_number_1st_part | 3 | uint16 | 1 | 1 | — | R | big_word_swap |