manufacturer: siemens
model: 7SK80
device: 7SK80
category: Altro
protocol: modbus
version: v1
firmware: null
verification: IMPORTED
isDemo: false
source:
  title: Import PDF com_modbus_7sj80_7sk80_7rw80_us.pdf
  url: null
  documentRef: null
  revision: null
generatedAt: 2026-09-21T14:31:46.964Z
registers:
  - address: "30001"
    addressNumeric: 0
    signal: ia
    name: Ia
    description: Corrente di fase A.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40001"
    addressNumeric: 0
    signal: hardware_designation_of_the_communication_module
    name: Hardware designation of the communication module
    description: 8 registri (stringa max 16 caratteri). "AME-GEN" per modulo AME,
      "AMO-GEN" per modulo AMO.
    functionCode: 3
    datatype: string
    length: null
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "1"
    addressNumeric: 1
    signal: 52_breaker_on
    name: 52 Breaker ON
    description: Comando doppio con indicazione di ritorno (checkback) sulla stessa
      posizione.
    functionCode: 1
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "30002"
    addressNumeric: 1
    signal: ib
    name: Ib
    description: Corrente di fase B.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "2"
    addressNumeric: 2
    signal: 52_breaker_off
    name: 52 Breaker OFF
    description: Comando doppio con indicazione di ritorno (checkback) sulla stessa
      posizione.
    functionCode: 1
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "30003"
    addressNumeric: 2
    signal: ic
    name: Ic
    description: Corrente di fase C.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30004"
    addressNumeric: 3
    signal: in
    name: In
    description: Corrente di neutro.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30005"
    addressNumeric: 4
    signal: va
    name: Va
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30006"
    addressNumeric: 5
    signal: vb
    name: Vb
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30007"
    addressNumeric: 6
    signal: vc
    name: Vc
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30008"
    addressNumeric: 7
    signal: va_b
    name: Va-b
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30009"
    addressNumeric: 8
    signal: vb_c
    name: Vb-c
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40009"
    addressNumeric: 8
    signal: communication_module_software_revision_major
    name: Communication module software revision (major)
    description: "MSB della revisione firmware del modulo di comunicazione. Es.: reg
      40009=0001H, reg 40010=0205H -> Revisione 1.2.5."
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30010"
    addressNumeric: 9
    signal: vc_a
    name: Vc-a
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40010"
    addressNumeric: 9
    signal: communication_module_software_revision_minor_patch
    name: Communication module software revision (minor.patch)
    description: LSB della revisione firmware del modulo di comunicazione, vedi 40009.
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30011"
    addressNumeric: 10
    signal: vn
    name: VN
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40011"
    addressNumeric: 10
    signal: mlfb_order_number_of_the_siprotec_device
    name: MLFB (order number) of the SIPROTEC device
    description: '16 registri (stringa max 32 caratteri). Es.:
      "7SJ80115EA903FA3----0D----------".'
    functionCode: 3
    datatype: string
    length: null
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30012"
    addressNumeric: 11
    signal: p
    name: P
    description: Potenza attiva.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MW
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30013"
    addressNumeric: 12
    signal: q
    name: Q
    description: Potenza reattiva.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MVAR
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30014"
    addressNumeric: 13
    signal: s
    name: S
    description: Potenza apparente.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MVA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30015"
    addressNumeric: 14
    signal: freq
    name: Freq
    description: null
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: Hz
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "30016"
    addressNumeric: 15
    signal: pf
    name: PF
    description: Power Factor. Scala 3.2767/32767.
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.0001
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40027"
    addressNumeric: 26
    signal: date_and_time_of_mapping_data_generation
    name: Date and time of mapping data generation
    description: '8 registri (stringa max 16 caratteri). Es.: "140106095747330" = 14
      gen 2006, 09:57:47.330.'
    functionCode: 3
    datatype: string
    length: null
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10034"
    addressNumeric: 33
    signal: 50_51_ph_act
    name: 50/51 PH ACT
    description: 1 = 50/51 O/C is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40035"
    addressNumeric: 34
    signal: number_of_selected_standard_mapping
    name: Number of selected standard mapping
    description: "MSB=numero mapping standard selezionato, LSB=byte alto della
      revisione mapping (continua nel registro 40036). Es.: reg 40035=3102H, reg
      40036=0304H -> Standard mapping 3-1, Revisione 2.3.4."
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10035"
    addressNumeric: 34
    signal: 50n_51n_act
    name: 50N/51N ACT
    description: 1 = 50N/51N is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40036"
    addressNumeric: 35
    signal: revision_of_mapping_data_low_word
    name: Revision of mapping data (low word)
    description: Completa la codifica della revisione del mapping, vedi 40035.
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10036"
    addressNumeric: 35
    signal: 50_n_51_n_pu
    name: 50(N)/51(N) PU
    description: 1 = 50(N)/51(N) O/C PICKUP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10037"
    addressNumeric: 36
    signal: 50_51_ph_a_pu
    name: 50/51 Ph A PU
    description: 1 = 50/51 Phase A picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10038"
    addressNumeric: 37
    signal: 50_51_ph_b_pu
    name: 50/51 Ph B PU
    description: 1 = 50/51 Phase B picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10039"
    addressNumeric: 38
    signal: 50_51_ph_c_pu
    name: 50/51 Ph C PU
    description: 1 = 50/51 Phase C picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10040"
    addressNumeric: 39
    signal: 50n_51n_pickedup
    name: 50N/51N Pickedup
    description: 1 = 50N/51N picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10041"
    addressNumeric: 40
    signal: 50_n_51_n_trip
    name: 50(N)/51(N) TRIP
    description: 1 = 50(N)/51(N) TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10042"
    addressNumeric: 41
    signal: pha_inrushblk
    name: PhA InrushBlk
    description: 1 = Phase A trip blocked by inrush detection
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10043"
    addressNumeric: 42
    signal: phb_inrushblk
    name: PhB InrushBlk
    description: 1 = Phase B trip blocked by inrush detection
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10044"
    addressNumeric: 43
    signal: phc_inrushblk
    name: PhC InrushBlk
    description: 1 = Phase C trip blocked by inrush detection
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "44"
    addressNumeric: 44
    signal: mode_remote
    name: Mode REMOTE
    description: Comando+indicazione sulla stessa posizione. 0=Set to LOCKED /
      LOCKED, 1=Set to UNLOCKED / UNLOCKED. Se non arriva nessun comando Modbus
      entro 5 minuti dallo sblocco, il dispositivo si riblocca automaticamente
      su LOCKED.
    functionCode: 1
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10045"
    addressNumeric: 44
    signal: inrush_x_blk
    name: INRUSH X-BLK
    description: "1 = Cross blk: PhX blocked PhY"
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "45"
    addressNumeric: 45
    signal: setting_group_a
    name: Setting Group A
    description: Comando+indicazione sulla stessa posizione. Scrivere 1 attiva il
      gruppo di parametri A (disattiva automaticamente quello attivo); scrivere
      0 e' rifiutato. Richiede il parametro "Change to Another Setting
      Group"=Protocol.
    functionCode: 1
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10046"
    addressNumeric: 45
    signal: 67_active
    name: 67 ACTIVE
    description: 1 = 67/67-TOC is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "46"
    addressNumeric: 46
    signal: setting_group_b
    name: Setting Group B
    description: Comando+indicazione sulla stessa posizione. Vedi Setting Group A
      per il comportamento di attivazione.
    functionCode: 1
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10047"
    addressNumeric: 46
    signal: 67n_active
    name: 67N ACTIVE
    description: 1 = 67N/67N-TOC is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "47"
    addressNumeric: 47
    signal: setting_group_c
    name: Setting Group C
    description: Comando+indicazione sulla stessa posizione. Vedi Setting Group A
      per il comportamento di attivazione.
    functionCode: 1
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10048"
    addressNumeric: 47
    signal: 67_67n_pickedup
    name: 67/67N pickedup
    description: 1 = 67/67N picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "48"
    addressNumeric: 48
    signal: setting_group_d
    name: Setting Group D
    description: Comando+indicazione sulla stessa posizione. Vedi Setting Group A
      per il comportamento di attivazione.
    functionCode: 1
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10049"
    addressNumeric: 48
    signal: 67_a_picked_up
    name: 67 A picked up
    description: 1 = 67/67-TOC Phase A picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10050"
    addressNumeric: 49
    signal: 67_b_picked_up
    name: 67 B picked up
    description: 1 = 67/67-TOC Phase B picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10051"
    addressNumeric: 50
    signal: 67_c_picked_up
    name: 67 C picked up
    description: 1 = 67/67-TOC Phase C picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10052"
    addressNumeric: 51
    signal: 67n_picked_up
    name: 67N picked up
    description: 1 = 67N/67N-TOC picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10053"
    addressNumeric: 52
    signal: 67_67n_trip
    name: 67/67N TRIP
    description: 1 = 67/67N TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10054"
    addressNumeric: 53
    signal: 46_active
    name: 46 ACTIVE
    description: 1 = 46 is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10055"
    addressNumeric: 54
    signal: 46_2_picked_up
    name: 46-2 picked up
    description: 1 = 46-2 picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10056"
    addressNumeric: 55
    signal: 46_1_picked_up
    name: 46-1 picked up
    description: 1 = 46-1 picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10057"
    addressNumeric: 56
    signal: 46_toc_pickedup
    name: 46-TOC pickedup
    description: 1 = 46-TOC picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10058"
    addressNumeric: 57
    signal: 46_trip
    name: 46 TRIP
    description: 1 = 46 TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10059"
    addressNumeric: 58
    signal: 81_active
    name: 81 ACTIVE
    description: 1 = 81 is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10060"
    addressNumeric: 59
    signal: 81_1_picked_up
    name: 81-1 picked up
    description: 1 = 81-1 picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10061"
    addressNumeric: 60
    signal: 81_2_picked_up
    name: 81-2 picked up
    description: 1 = 81-2 picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10062"
    addressNumeric: 61
    signal: 81_1_trip
    name: 81-1 TRIP
    description: 1 = 81-1 TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10063"
    addressNumeric: 62
    signal: 81_2_trip
    name: 81-2 TRIP
    description: 1 = 81-2 TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10064"
    addressNumeric: 63
    signal: 27_active
    name: 27 ACTIVE
    description: 1 = 27 Undervoltage protection is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40065"
    addressNumeric: 64
    signal: milliseconds
    name: Milliseconds
    description: Registro di trasferimento data/ora.
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10065"
    addressNumeric: 64
    signal: 27_1_picked_up
    name: 27-1 picked up
    description: 1 = 27-1 Undervoltage picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40066"
    addressNumeric: 65
    signal: hours_minutes
    name: Hours / Minutes
    description: Byte alto=Ore, byte basso=Minuti.
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10066"
    addressNumeric: 65
    signal: 27_1_trip
    name: 27-1 TRIP
    description: 1 = 27-1 Undervoltage TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40067"
    addressNumeric: 66
    signal: month_day
    name: Month / Day
    description: Byte alto=Mese, byte basso=Giorno.
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10067"
    addressNumeric: 66
    signal: 59_active
    name: 59 ACTIVE
    description: 1 = 59-Overvoltage protection is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40068"
    addressNumeric: 67
    signal: time_date_status_byte_year
    name: Time/Date status byte / Year
    description: Byte alto=byte di stato data/ora, byte basso=Anno.
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "10068"
    addressNumeric: 67
    signal: 59_1_picked_up
    name: 59-1 picked up
    description: 1 = 59 picked up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40069"
    addressNumeric: 68
    signal: set_time_and_date
    name: Set Time and Date
    description: Disponibile solo se la sincronizzazione oraria e' configurata con
      l'uso di questo registro.
    functionCode: 6
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: WRITE
    endianness: null
    group: null
    notes: null
  - address: "10069"
    addressNumeric: 68
    signal: 59_1_trip
    name: 59-1 TRIP
    description: 1 = 59 TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10070"
    addressNumeric: 69
    signal: 50ns_67ns_act
    name: 50Ns/67Ns ACT
    description: 1 = 50Ns/67Ns is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10071"
    addressNumeric: 70
    signal: 64_pickup
    name: 64 Pickup
    description: 1 = 64 displacement voltage pick up
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10072"
    addressNumeric: 71
    signal: 64_trip
    name: 64 TRIP
    description: 1 = 64 displacement voltage element TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10073"
    addressNumeric: 72
    signal: 50ns_2_pickup
    name: 50Ns-2 Pickup
    description: 1 = 50Ns-2 Pickup
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10074"
    addressNumeric: 73
    signal: 50ns_2_trip
    name: 50Ns-2 TRIP
    description: 1 = 50Ns-2 TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10075"
    addressNumeric: 74
    signal: 50ns_1_pickup
    name: 50Ns-1 Pickup
    description: 1 = 50Ns-1 Pickup
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10076"
    addressNumeric: 75
    signal: 50ns_1_trip
    name: 50Ns-1 TRIP
    description: 1 = 50Ns-1 TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10077"
    addressNumeric: 76
    signal: sens_gnd_ph_a
    name: Sens. Gnd Ph A
    description: 1 = Sensitive ground fault picked up in phase A
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10078"
    addressNumeric: 77
    signal: sens_gnd_ph_b
    name: Sens. Gnd Ph B
    description: 1 = Sensitive ground fault picked up in phase B
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10079"
    addressNumeric: 78
    signal: sens_gnd_ph_c
    name: Sens. Gnd Ph C
    description: 1 = Sensitive ground fault picked up in phase C
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10080"
    addressNumeric: 79
    signal: sensgnd_forward
    name: SensGnd Forward
    description: 1 = Sensitive ground fault in forward direction
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10081"
    addressNumeric: 80
    signal: sensgnd_reverse
    name: SensGnd Reverse
    description: 1 = Sensitive ground fault in reverse direction
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10082"
    addressNumeric: 81
    signal: 66_active
    name: 66 ACTIVE
    description: 1 = 66 Motor start protection is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10083"
    addressNumeric: 82
    signal: 66_trip
    name: 66 TRIP
    description: 1 = 66 Motor start protection TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10084"
    addressNumeric: 83
    signal: start_sup_act
    name: START-SUP ACT
    description: 1 = Startup supervision is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10085"
    addressNumeric: 84
    signal: start_sup_trip
    name: START-SUP TRIP
    description: 1 = Startup supervision TRIP
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10086"
    addressNumeric: 85
    signal: start_sup_pu
    name: START-SUP pu
    description: 1 = Startup supervision Pickup
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10087"
    addressNumeric: 86
    signal: 74tc_active
    name: 74TC ACTIVE
    description: 1 = 74TC Trip circuit supervision is ACTIVE
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10088"
    addressNumeric: 87
    signal: fail_trip_cir
    name: "FAIL: Trip cir."
    description: 1 = 74TC Failure Trip Circuit
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10089"
    addressNumeric: 88
    signal: cntrl_auth
    name: Cntrl Auth
    description: 1 = Control authority (0=REMOTE, 1=LOCAL)
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "10090"
    addressNumeric: 89
    signal: modelocal
    name: ModeLOCAL
    description: 1 = Control mode LOCAL (0=LOCKED, 1=UNLOCKED)
    functionCode: 2
    datatype: boolean
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40129"
    addressNumeric: 128
    signal: diagnostics_word
    name: Diagnostics word
    description: bit0 Device OK(1=aggiornamento della replica del dispositivo
      completato dopo avvio/riavvio); bit1 Settings Calc.(1=calcolo impostazioni
      in corso); bit2 ProtActive(1=almeno una funzione di protezione attiva);
      bit3 Error Sum Alarm(1=allarme sommario di errore attivo); bit4 Alarm Sum
      Event(1=evento sommario di allarme attivo); bit5 Relay PICKUP(1=segnale di
      gruppo PICKUP); bit6 Relay TRIP(1=comando TRIP generale); bit8 Test
      mode(1=modalita' test attiva); bit15 Data invalid(1=dati nel messaggio
      Modbus non validi, generata dallo slave Modbus). Leggibile anche con
      funzione Diagnostics(FC8), sottofunzione Return Diagnostic Register.
    functionCode: 3
    datatype: bitfield
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40201"
    addressNumeric: 200
    signal: wp_puls_pulsed_energy_wp_active
    name: Wp(puls) - Pulsed Energy Wp (active)
    description: "Impulsi di energia attiva contati su ingresso binario. Scala:
      2^31-1 impulsi = fondo scala. Riferimento: 60000 impulsi/ora per V=Vnom e
      I=Inom (parametri 1101/1102)."
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40203"
    addressNumeric: 202
    signal: wq_puls_pulsed_energy_wq_reactive
    name: Wq(puls) - Pulsed Energy Wq (reactive)
    description: Impulsi di energia reattiva contati su ingresso binario. Vedi 40201
      per la scala di riferimento.
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40205"
    addressNumeric: 204
    signal: wpforward_wp_forward
    name: WpForward - Wp Forward
    description: Energia attiva contatore derivato dai valori misurati. Vedi 40201
      per la scala di riferimento.
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40207"
    addressNumeric: 206
    signal: wqforward_wq_forward
    name: WqForward - Wq Forward
    description: Energia reattiva contatore derivato dai valori misurati. Vedi 40201
      per la scala di riferimento.
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40209"
    addressNumeric: 208
    signal: wpreverse_wp_reverse
    name: WpReverse - Wp Reverse
    description: Energia attiva inversa, contatore derivato dai valori misurati.
      Vedi 40201 per la scala di riferimento.
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40211"
    addressNumeric: 210
    signal: wqreverse_wq_reverse
    name: WqReverse - Wq Reverse
    description: Energia reattiva inversa, contatore derivato dai valori misurati.
      Vedi 40201 per la scala di riferimento.
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 1
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40301"
    addressNumeric: 300
    signal: ia_primary_fault_current
    name: Ia - Primary fault current
    description: null
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 0.01
    offset: 0
    unit: kA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40303"
    addressNumeric: 302
    signal: ib_primary_fault_current
    name: Ib - Primary fault current
    description: null
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 0.01
    offset: 0
    unit: kA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40305"
    addressNumeric: 304
    signal: ic_primary_fault_current
    name: Ic - Primary fault current
    description: null
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 0.01
    offset: 0
    unit: kA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40311"
    addressNumeric: 310
    signal: sum_ia_accumulation_of_interrupted_current_ph_a
    name: Sum Ia - Accumulation of interrupted current Ph A
    description: null
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 0.01
    offset: 0
    unit: kA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40313"
    addressNumeric: 312
    signal: sum_ib_accumulation_of_interrupted_current_ph_b
    name: Sum Ib - Accumulation of interrupted current Ph B
    description: null
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 0.01
    offset: 0
    unit: kA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40315"
    addressNumeric: 314
    signal: sum_ic_accumulation_of_interrupted_current_ph_c
    name: Sum Ic - Accumulation of interrupted current Ph C
    description: null
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 0.01
    offset: 0
    unit: kA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40317"
    addressNumeric: 316
    signal: op_hours_counter_of_operating_hours
    name: Op.Hours - Counter of operating hours
    description: null
    functionCode: 3
    datatype: uint32
    length: 2
    scale: 1
    offset: 0
    unit: h
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40351"
    addressNumeric: 350
    signal: ia_min
    name: Ia Min
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40356"
    addressNumeric: 355
    signal: ia_max
    name: Ia Max
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40361"
    addressNumeric: 360
    signal: ib_min
    name: Ib Min
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40366"
    addressNumeric: 365
    signal: ib_max
    name: Ib Max
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40371"
    addressNumeric: 370
    signal: ic_min
    name: Ic Min
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40376"
    addressNumeric: 375
    signal: ic_max
    name: Ic Max
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: A
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40381"
    addressNumeric: 380
    signal: va_nmin
    name: Va-nMin
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40386"
    addressNumeric: 385
    signal: va_nmax
    name: Va-nMax
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40391"
    addressNumeric: 390
    signal: vb_nmin
    name: Vb-nMin
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40396"
    addressNumeric: 395
    signal: vb_nmax
    name: Vb-nMax
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40401"
    addressNumeric: 400
    signal: vc_nmin
    name: Vc-nMin
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40406"
    addressNumeric: 405
    signal: vc_nmax
    name: Vc-nMax
    description: Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40411"
    addressNumeric: 410
    signal: vn_min
    name: Vn Min
    description: V neutro. Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40416"
    addressNumeric: 415
    signal: vn_max
    name: Vn Max
    description: V neutro. Seguito da 4 registri con data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: kV
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40421"
    addressNumeric: 420
    signal: pmin
    name: Pmin
    description: Potenza attiva minima. Seguito da 4 registri con data/ora
      dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MW
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40426"
    addressNumeric: 425
    signal: pmax
    name: Pmax
    description: Potenza attiva massima. Seguito da 4 registri con data/ora
      dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MW
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40431"
    addressNumeric: 430
    signal: qmin
    name: Qmin
    description: Potenza reattiva minima. Seguito da 4 registri con data/ora
      dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MVAR
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40436"
    addressNumeric: 435
    signal: qmax
    name: Qmax
    description: Potenza reattiva massima. Seguito da 4 registri con data/ora
      dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MVAR
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40441"
    addressNumeric: 440
    signal: smin
    name: Smin
    description: Potenza apparente minima. Seguito da 4 registri con data/ora
      dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MVA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40446"
    addressNumeric: 445
    signal: smax
    name: Smax
    description: Potenza apparente massima. Seguito da 4 registri con data/ora
      dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: MVA
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40451"
    addressNumeric: 450
    signal: fmin
    name: fmin
    description: Frequenza minima. Seguito da 4 registri con data/ora dell'evento
      (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: Hz
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40456"
    addressNumeric: 455
    signal: fmax
    name: fmax
    description: Frequenza massima. Seguito da 4 registri con data/ora dell'evento
      (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.01
    offset: 0
    unit: Hz
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40461"
    addressNumeric: 460
    signal: pf_min
    name: PF Min
    description: "Power Factor minimo. ATTENZIONE: il documento riporta la scala
      come \"3.767\" (anziche' \"3.2767\" come per PF Max): probabile refuso,
      riportato cosi' com'e' senza correggere. Seguito da 4 registri con
      data/ora dell'evento (non importati)."
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.000115
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "40466"
    addressNumeric: 465
    signal: pf_max
    name: PF Max
    description: Power Factor massimo. Scala 3.2767/32767. Seguito da 4 registri con
      data/ora dell'evento (non importati).
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.0001
    offset: 0
    unit: null
    access: READ
    endianness: null
    group: null
    notes: null