manufacturer: generic
model: XY-MD02
device: XY-MD02
category: Altro
protocol: modbus
version: v1
firmware: null
verification: IMPORTED
isDemo: false
source:
  title: Import PDF temperatura_xy-md02-manual.pdf
  url: null
  documentRef: null
  revision: null
generatedAt: 2026-09-21T14:44:02.992Z
registers:
  - address: "1"
    addressNumeric: 1
    signal: temperature
    name: Temperature
    description: "Valore hex con segno: es. 0x0131=305 → 30.5°C; 0xFF33=-205 → -20.5°C."
    functionCode: 4
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: °C
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "2"
    addressNumeric: 2
    signal: humidity
    name: Humidity
    description: Es. 0x0222=546 → 54.6%RH.
    functionCode: 4
    datatype: uint16
    length: 1
    scale: 0.1
    offset: 0
    unit: "%RH"
    access: READ
    endianness: null
    group: null
    notes: null
  - address: "257"
    addressNumeric: 257
    signal: device_address
    name: Device Address
    description: Indirizzo slave Modbus, 1-247 (default 1).
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "258"
    addressNumeric: 258
    signal: baud_rate
    name: Baud Rate
    description: 0 = 9600, 1 = 14400, 2 = 19200.
    functionCode: 3
    datatype: uint16
    length: 1
    scale: 1
    offset: 0
    unit: null
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "259"
    addressNumeric: 259
    signal: temperature_correction
    name: Temperature Correction
    description: Offset di calibrazione temperatura, range -10.0~10.0°C.
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: °C
    access: READ_WRITE
    endianness: null
    group: null
    notes: null
  - address: "260"
    addressNumeric: 260
    signal: humidity_correction
    name: Humidity Correction
    description: Offset di calibrazione umidita', range -10.0~10.0%RH.
    functionCode: 3
    datatype: int16
    length: 1
    scale: 0.1
    offset: 0
    unit: "%RH"
    access: READ_WRITE
    endianness: null
    group: null
    notes: null